Idealec : infinitely skilled

Idealec Bus Bars: ID Tronic

 pictos_radio.gifpictos_ordi.gif

Applications

Cabinet power distribution for different types of electronic systems (telecommunication, mobile telephony base station, servers, data storage bays, inverters, power distribution panels, etc.).


 

Description

Co-laminated structure (cross-section)

Idealec busbar : co-laminated structure

Specifications

Voltage (AC/DC)380V max.
Power250A max.
Temperature range-40°C to +95°C
Relative humidity85% max.
Electrical conductorCopper, copper alloys and aluminium
InsulationPolyester dielectric film
Support and shieldingSteel, stainless steel, galvanised steel, aluminium
Electrical tests applicable to qualificationHigh pot test (<2500V), electrical continuity, contact resistance, insulation resistance at 500V, capacitance
Electrical tests applicable in productionHigh pot test (<2500V), electrical continuity, contact resistance, insulation resistance at 500V
Applicable certificationsRoHS, UL94, UL1850, UL1015...

Connections

Cable equipped with lug. Waterproof protection availableCable equipped with lug. Waterproof protection availableConnection hardware for plug-in circuit-breakerConnection hardware for plug-in circuit-breaker
Cable equipped with contactsCable equipped with contactsConnector installed on Bus BarConnector installed on Bus Bar
Harness equipped with connectorsHarness equipped with connectorsFast-on® tabsFast-on® tabs
Fastened threaded insertFastened threaded insertFastened fixed spacerFastened fixed spacer

Components

Protection fuseProtection fusePrinted circuitPrinted circuit
Circuit-breakerCircuit-breakerInterlock contactorInterlock contactor
Power connectorPower connectorCableCable
Mixed data/power connectorMixed data/power connector  
In partnership with FCI